Rittal Power Management

Modular compact system with distribution!

RimatriX5     |     Rack     Power     Cooling     Security     Monitoring     |     Service & Support     Contact
  Overview | System solutions
  Greater freedom | Greater flexibility
Greater reliability | Products
  PMC 200 | PMC 12 | PDR, PDM | PSM | PSM Plus
Monitoring | System integration | Products
  Definition of application | Room-based IT climate control
Rack-specific IT climate control | Complete solutions
Infrastructure for IT climate control | Products
  CMC | Security modules | Video monitoring
Fire prevention and extinguisher system | Products
  KVM technology | RiWatchIT V3
Products
  Project management | Service chain
Rittal service packages | References Downloads
  Hotline | Rittal Global

System integration

19" sub-distributor

The sub-distributor is mounted directly in the UPS enclosure. This allows a compact complete system to be realised with a 0.6 m2 footprint that contains rack-mounted modular UPS, batteries and distribution.
The distributor is installed in the rear area of the enclosure where the PSM busbars (installed in the racks) are attached directly to the cables using plug connectors. Twelve three-phase outlets are available on the distributor, this means a maximum of twelve racks can be supplied. In addition, 10 A circuit-breakers are integrated for each phase. These components are optimally adapted to the 12 and 20 kW N+1 UPS systems.

Application areas in 12 and 20 kW UPS
The twelve-way sub-distributor is used in combination with the modular UPS. The server racks can be attached directly using plug & play technology.

Technical specifications:
• 482,6 mm (19"), 6 U
• 12 outlets, three-phase , 400 V/50 Hz with 10 A
• 10 A circuit-breaker per phase, class C

Static Transfer Switch (STS)

The use of a static transfer switch allows "single-corded devices" (devices that have only one power pack) to be operated with a redundant power supply. STS has two infeeds that are switched automatically. The switching time is less than 5 ms. This ensures that sensitive devices can be operated without interference. The “Break before Make” transfer ensures that the load is not fed concurrently from two sources.

Operation
The operating panel mounted on the housing front shows all central functions and messages of the Static Transfer Switch. All messages may also be evaluated with floating contacts. The STS may optionally be supplemented with a quickchange frame equipped with an external bypass. This function allows the load to be switched manually onto the mains for servicing purposes.

Connectivity
The optional SNMP card makes it possible for the Static Transfer Switch STS to be integrated in a network management system. The web server integrated in the SNMP card provides password-protected access to the STS using a web browser.

Version
• STS 16 A without serial interface
• STS 16 A with serial interface
• STS 16 A with serial interface
  and quick change frame
• STS 20 A with serial interface
  and quick-change frame

Monitoring & Remote Management Power Rack Security Cooling

 
RimatriX5 - Driving IT-Performance